Power transformer have many Specification Types.Normally, they are classified by Voltage, Capacity,Cooling Methods etc.

power transformer tank with corrugated fin wall
According to voltage, transformer specifications can be divided into: 36 volts, 110 volts, 0.4 kilovolts, 10 kilovolts, 22 kilovolts, 6 kilovolts, 35 kilovolts, 110 kilovolts, 220 kilovolts, 350 kilovolts, 200 kilovolts, 500 kilovolts, 250 kilovolts, 600 kilovolts.
According to capacity, the rated capacity of Chinese transformers is calculated according to the priority factor of R10, i.e. Calculate by multiples of 10 to the 10th power, 50KVA, 80KVA, 100KVA, etc.
The type of transformer is: transformer winding number + phase number + cooling mode + forced oil circulation + on-load or No-load voltage regulation + design serial number +”-“+capacity + rated voltage at high voltage side.
For Example: SFPZ9-120000/110
It refers to three-phase (double winding transformer omits the number of windings, if it is three windings, there is an S ahead)
Dual-winding forced oil circulation air-cooled on-load voltage regulation, transformer with design serial number 9, capacity 120 000 KVA and rated voltage 110 KV on high voltage side

Power Transformer Classification:

1.By Cooling mode:

Dry (self-cooling) transformer, oil-immersed (self-cooling) transformer and fluoride (evaporative cooling) transformer.
Oil immersed transformer also named oil filled transformer. It adopts Corrugated Fin Cooler Wall to cooler the transformer oil.The Corrugated Radiator is weld together with transformer tank body.

USAGE OF CORRUGATED FIN PRODUCTION LINE

2.By Moisture-proof methods:

Open transformer, encapsulated transformer and sealed transformer.

3.By core or coil structure:

Core transformer (insert core, C core, ferrite core), shell transformer (insert core, C core, ferrite core), ring transformer, metal foil transformer

4.According to the number of power supply phases:

Single-phase transformer, three-phase transformer and multi-phase transformer.

5.Classified by use:

Power transformer, Voltage regulating transformer, Audio transformer, Intermediate frequency transformer, High frequency transformer, Pulse transformer.

Characteristic parameters of power transformer

1. Working frequency

Transformer core loss has a great relationship with frequency, so it should be designed and used according to the use frequency, which is called working frequency.

2. Rated power

Under the specified frequency and voltage, the transformer can work for a long time without exceeding the output power of the specified temperature rise.

3. Rated voltage

The voltage allowed to be applied on the coil of the transformer shall not be greater than the specified value in operation.

4. Voltage Ratio

Refers to the ratio of primary voltage to secondary voltage of transformer. There are differences between no-load voltage ratio and load voltage ratio.

5. No-load Current

When transformer secondary open circuit, the primary still has a certain current, which is called no-load current. The no-load current consists of magnetization current (producing flux) and iron loss current (caused by core loss). For 50Hz power transformer, no-load current is basically equal to magnetization current.

6. No-load Loss

It refers to the power loss measured at the primary stage when the secondary transformer is open. The main loss is the core loss, followed by the loss of no-load current on the primary coil copper resistance (copper loss), which is very small.

7. Efficiency

Percentage of the ratio of secondary power P2 to primary power P1. Usually the higher the rated power of transformer, the higher the efficiency.

8. Insulation Resistance

Indicates the insulation performance between transformer coils and between coils and cores. The insulation resistance is related to the performance, temperature and humidity of the insulating materials used.

Transformer Corrugated Cooler Wall Manufacturing Related Machines:

Automatic Corrugated Fins Wall Manufacturing Line


CORRUGATED FIN FOLDING AND WELDING MACHINES

Corrugated Fins Wall Forming Machine


corrugated fins wall making machine

Full-auto PLC Corrugated Fins Seam Welding Machine


corrugated fins wall seam welding machine

Hydraulic Decoiler


steel roll feeding machine

Corrugated Fins Wall Leak Testing Machine


corrugated fin wall leakage test machine

Want to know more?(Marketing Title)

Phone: 008615195010186
Email: cnkylt@aliyun.com

评论

此博客中的热门博文

SIMPLIFIED DRAWING METHOD FOR MECHANICAL DRAWING

When design  machine parts  /  prototypes  by 2D engineering method, we can adopt simplified drawing method: 1.When the object ( mechanical part ) has several identical structures (teeth, slots, etc.) and distributes according to certain rules, only a few complete structures need to be drawn. The rest are connected by fine lines, and the total number of structures is indicated. Mechanical part  Examples of Simplified Drawing of Mechanical Drawings : Examples of Simplified Drawing of Mechanical Drawings for Same Structure and Simplified Drawing Same Structure and Simplified Drawing 2.A number of holes with the same diameter and regular distribution (round holes, screw holes, sinks, etc.) can be drawn only one or several, the rest can only be represented by the center line, and the total number of holes should be indicated when the size of holes is marked in the figure. Simplified Drawing Method for Regularly Distributed Holes Simplified Drawing ...

WHY SCREW THREAD CAN NOT PASS THREAD GAUGE INSPECTION

After the first metal part be tapped, we always to check it: if pass the thread gauge inspection? The inspection result is OK, we can do mass production. If it fails, We should consider which reasons cause tapping faiulre. KYLT provide Metal Machining services for:  WEDM, EDM, DRILL, TAPPING ,  CNC LATHING ,  CNC MILLING ,  ALUMINUM / MAGNESIUM / PLASTIC RAPID PROTOTYPES MAKING . 1PCS ORDER IS ALLOWED. Aluminum CNC machined workpiece Normally, the following reasons may cause screw thread faiulre: 1) UNQUALIFIED TAP Tap is wear or bad 2) QUALIFIED DRILLING HOLE (BEFORE TAPPING) If the hole is too small, because of friction, will increase the difficulty of tapping, while tapping faster wear, and vice versa, the hole is too big, it can easily tap into, but the quality of teeth is very poor, because the diameter of teeth will become larger, relative to the screw nut bonding force is insufficient, easy to slide teeth. In M3 *0.5, the correct hole (general i...

CNC MILLING: DOWN MILLING &UP MILLING

CNC milling  process adopt  Down milling  or  Up milling ? Which milling method is better? Down Milling & Up Milling Definition Down milling:  refers to the cutting speed direction of the cutter is the same as the moving direction of the workpiece. Up milling : refers to the direction of cutting speed opposite to the direction of movement of the workpiece. CNC milling work, How to distinguish Down Milling and Up Milling. WHEN MILLING WORKPIECE OUTLINE: Clockwise feeding and programming along the outline of the workpiece is Down milling. Counterclockwise programming and feeding along the outline of the workpiece is Up milling. WHEN MILLING THE INNER CONTOUR OF THE WORKPIECE: Clockwise feeding and programming along the inner contour of the workpiece is downmilling. Counterclockwise programming and feeding along the inner contour of the workpiece is reverse milling. CNC UP & DOWN MILLING CHARACTERISTICS OF DOWN MILLING AND UP MILLI...