Oil filled transformer test & trial operation

After Oil immersed transformer be installed, we should do testing works as follows:

1. Telemetry of insulation resistance:

(1) Telemetry project, high pressure to low pressure and ground (shell), low pressure to high pressure and ground (shell)
(2)Select 2500V megohm meter, the appearance of megohm meter should be good, complete shell, flexible shake handle, no long resistance pointer, no glass damage.
(3) Open circuit test of megawatt-hour meter, separate two pens, shake the handle of megawatt-hour meter up to 120 y/min, the needle pointing to infinite (∞) is better. Short circuit test: shake the handle of megawatt-hour meter, overlap two than instantaneous, the needle pointing to “0” (zero), indicating that megawatt-hour meter is normal.
(4) Qualified value: at 20℃+, the new transformer is not less than 450 MΩ, and the operation is not less than 300 MΩ. This value should not be reduced by 30% compared with the previous value.
(5)Absorption ratio R60/R12 should be 1.3 times at 10-30℃

2. DC resistance measurement:

It can measure the welding quality of transformer internal conductor and lead, whether the parallel branch connection is correct, whether there is interlayer short circuit or internal break, tap-changer, whether the contact between bushing and lead is good, etc.

3. Measurement method:

bridge can be used to measure, direct reading, high accuracy, no bridge can use voltage drop method, voltage drop method to measure DC resistance wiring a) measurement of small resistance b) measurement of large resistance 1 – measured coil 2 – knife gate 3 – accumulator 4 – voltmeter 5 – ammeter DC resistance calculation formula: U – voltmeter reading (mv) I – ammeter reading (A) with tap switch Transformers of 1.5% shall be measured at all tap positions during handover or overhaul. When a three-phase transformer has a neutral point due to the outlet line, the resistance of each phase line diagram should be measured. When there is no neutral point outlet line, the resistance of the line can be measured.
When measuring, all non-tested line diagrams should be open and not short-connected. When measuring, we must wait for the current to stabilize before reading. We should pay attention to personal safety.

4. Judgment criteria:

The difference between DC resistance of each phase diagram should not be greater than 2% of the three average values, and the relative change should not be greater than 2% compared with previous measurements. In order to compare with the measured values in the factory or in the past, the DC resistance values should be converted to the same temperature values.
The formula is as follows: R1=R2*(T+Δt1)/(T+Δt2). For copper conductors, the T value is 235; for aluminium conductors, the T value is 225. Formula: R1 – converted DC resistance value at t℃, R2 – current temperature resistance value, Δt1 and Δt2 represent the corresponding temperature (℃) value of conductor respectively.
For example, if you know that the resistance of a copper conductor at 30℃ is R30, then the resistance of the conductor at 60℃ is: R60 = R30* (235+60)/(235+30)= R30*295/265 = 1.113*R30.

Oil immersed transformer test Failure reasons:

(1)Poor contact of tap changer
(2)The coil or lead is badly welded and broken.
(3)Poor connection between conductive rod and lead of casing
(4)Interturn or interlayer short circuit of coil.

5.Oil immersed transformer Group test:

(1) Polarity measurement by single-phase transformer. The purpose of three-phase transformer measurement group is to make correct connection and judge whether the transformer can operate in parallel.
(2) Polarity measurement: DC and AC measurements can be used. In addition, DC measurements are introduced: DC test wiring chooses 2-4V batteries and zero position in the central DC voltmeter. At the moment of closing, the meter needle swings in the positive direction, while at the moment of opening, the meter needle swings in the negative direction, which reduces polarity. On the contrary, add polarity.
(3) There are DC method and AC method to determine the connection group of three-phase transformer.

full auto corrugated fins wall manufacturing line
full auto corrugated fins wall manufacturing line

Oil immersed transformer trial operation:

1. Transformers can be tested only after all test items are qualified.
2. Before commissioning, a comprehensive inspection of transformers should also be carried out.
3. The transformer is subjected to five impact tests (closing tests).
4. No-load operation time is related to transformer capacity, generally no less than 24 hours.
5. After no-load operation time is completed, the transformer will be reloaded.

Oil immersed Distribution Transformer Corrugated Tank Wall Manufacturing Related Machines:

automatic transformer corrugated cooler wall production line
automatic transformer corrugated cooler wall production line

 

Automatic Corrugated Fins Wall Manufacturing Line


CORRUGATED FIN TRANSFORMER TANK WALL FOLDING AND WELDING MACHINES
CORRUGATED FIN TRANSFORMER TANK WALL FOLDING AND WELDING MACHINES

Corrugated Fins Wall Forming Machine


Transformer tank corrugated fins wall making machine
Transformer tank corrugated fins wall making machine


Full-auto PLC Corrugated Fins Seam Welding Machine


automatic transformer tank corrugated folded wall seam welding machine
automatic transformer tank corrugated folded wall seam welding machine

Automatic Hydraulic Decoiler steel roll feeding machine


hydraulic steel roll feeding machine
hydraulic steel roll feeding machine


Corrugated Fins Wall Leak Testing Machine



transformer tank corrugated fin wall leakage test machine
transformer tank corrugated fin wall leakage test machine


Want to know more?(Marketing Title)

Phone: 008615195010186
Email: cnkylt@aliyun.com

评论

此博客中的热门博文

CNC MACHINE BE CLASSIFIED BY SERVO CONTROL MODE

Servo control mode to classify CNC machine tool. (1) open loop control CNC machine tool The feed servo drive of this kind of machine tool is open-loop, that is, there is no detection feedback device. Generally, its driving motor is a stepping motor. The main feature of stepping motor is that every time the control circuit changes the command pulse signal, the motor will rotate a step angle, and the motor itself has self-locking ability. The drive circuit is controlled by the pulse distributor, which controls the coordinate displacement by changing the number of pulses, the displacement speed by changing the frequency of pulses, and the direction of displacement by changing the distribution sequence of pulses. Therefore, this control mode is characterized by convenient control, simple structure and low price. The command signal flow from the CNC system is unidirectional, so there is no stability problem of the control system, but because the error of the mechanical transmission...

SELECTION PRINCIPLE OF CUTTING PARAMETERS FOR SCREW THREAD TURNING

Because the pitch (or lead) of the thread is specified by the drawing, the key to choose the cutting parameters when  turning  the screw thread is to determine the spindle speed n and the cutting depth AP. 1) SELECTION OF SPINDLE SPEED TO DO SCREW THREAD TURNING According to the mechanism that the spindle turns 1 and the cutter feeds 1 lead when turning the thread, the feed speed of the CNC lathe is determined by the selected spindle speed. The thread lead (which is the pitch when the thread is single head thread) instructed in the thread processing program section is equivalent to the feed speed VF VF = n f (1) expressed by the feed rate f (mm / R) From Formula 1, it can be seen that the feed speed VF is proportional to the feed amount F. if the spindle speed of the machine tool is selected too high, the converted feed speed will greatly exceed the rated feed speed of the machine tool. Therefore, when selecting the rotation speed of the main shaft for turning the threa...

SCREW THREAD MACHINING METHOD

In  Metal parts machining  works, screw thread (tapping) be required. The screw thread is mainly divided into: connecting thread and driving thread For  connecting thread , the main  machining  methods are: tapping, threading, turning, rolling, etc. For  transmission thread , the main  machining methods  are: rough and fine turning – grinding;whirlwind  milling  – rough and fine  turning , etc. CNC turned screw thread part The following describes the various screw machining methods: THREAD CUTTING Generally, it refers to the method of machining thread on workpiece with forming tool or grinding tool, mainly including  turning , milling, tapping, threading, grinding and whirlwind cutting, etc. THREAD MILLING On the thread milling machine, the disc milling cutter or comb milling cutter is used for milling. Disc  milling  cutter is mainly used for milling trapezoid external thread of screw rod, worm and o...